Size finder · Swift EAPS

Which Swift automatic phase changer do I need?

Count what runs in your house. We suggest a rating.

Lights, fans and the fridge are counted for you.

Air conditioners
Water heating and pump

On the geyser's label. Most are 2 kW.

Only a single-phase pump. Enter 0 if none.

Backup and the rest

Oven, motor, heater: their kW.

Find my model

Suggested model

Estimate

EAPS-60

Suggested model: EAPS-60. Your load comes to about 12 kVA.

EAPS-60 is rated 60 A, 12 kVA. Brochure guide: lighting load plus two 1.5-ton ACs.

Your load uses all of its rating (12 of 12 kVA). Planning to add a load? Choose the EAPS-90.

See the Swift EAPS-60 automatic phase changer
4060901201501802700 kVA60 kVA
Bar: your load. Ticks: each EAPS model's rating (40 = EAPS-40, 8 kVA).
How we added it up
Load allowances
Lights, fans and fridge4 kVA
2 1.5-ton ACs8 kVA
Total12 kVA
Estimate; we confirm the rating before you buy.

How it works

Each model is sized by 1.5-ton ACs, plus your lighting load.

Swift EAPS models and their recommended loads
ModelRatingLighting load plus
EAPS-4040 A, 8 kVAone 1.5-ton AC
EAPS-6060 A, 12 kVAtwo 1.5-ton ACs
EAPS-9090 A, 18 kVAthree 1.5-ton ACs
EAPS-120120 A, 24 kVAfour 1.5-ton ACs
EAPS-150150 A, 30 kVAfive 1.5-ton ACs
EAPS-180180 A, 36 kVAsix 1.5-ton ACs
EAPS-270270 A, 54 kVAseven 1.5-ton ACs

The finder suggests the smallest model that passes two checks. Its rating covers your whole load in kVA. And its brochure line covers your ACs: five 1.5-ton ACs need at least the EAPS-150, even if the kVA would fit a smaller model.

A 1-ton AC counts as two-thirds of a 1.5-ton AC, and a 2-ton AC as one and a third. More than seven 1.5-ton ACs is beyond one EAPS-270: you need more than one unit or a larger panel, so ask us.

What we count for each item

Load allowances used by the size finder
ItemWe count
Lights, fans, fridge4 kVA together
1.5-ton AC4 kVA each
1-ton AC2.7 kVA each
2-ton AC5.3 kVA each
GeyserIts kW (2 kW = 2 kVA)
Single-phase pump2.5 kVA per HP, for the starting surge
UPS or inverterIts kVA
Anything elseIts kW

Why the whole load, not one phase?

If two phases fail, your whole load runs on the one live phase. So the finder counts everything, not one phase.