How much kVAR do you need?

Enter your load and your PF. See the kVAR to reach your target.

Your load

Your average load while the machines run.

Your present power factor

For example 0.78.

Starts at 0.99. Anything from 0.90 to 0.99.

See the result

kVAR needed

Estimate

33kVAR

You need about 33 kVAR to raise PF from 0.78 to 0.99.

AEE series APFC panel, about 35 kVAR.

5 to 18 stages; we size the steps to your load.

Load
50 kW
PF now → target
0.78 → 0.99
kVAR, exact
32.99
Panel step
35 kVAR
50 kW33 kVARfrom the panelPF 0.78PF 0.99
Solid: your supply now. Dashed: at the target PF. The thick line is what the panel supplies.
Estimate; we confirm the panel size from your bill and load. kVAR = kW × (tan(cos⁻¹ PF now) − tan(cos⁻¹ target PF)).

What to enter

How it works

The calculator uses the standard formula:

kVAR = kW × (tan(cos⁻¹ present PF) − tan(cos⁻¹ target PF))

Example: 50 kW at PF 0.78, with a target of 0.99. That needs about 33 kVAR.

The result is then rounded up to a panel size. Our APFC panels run from 4.5 to 150 kVAR. They have 5 to 18 stages; we size the steps to your load. Contactors switch each stage.

kVAR for each kW of load, target PF 0.99

Multiply your load in kW by the figure for your present PF.

kVAR needed for each kW of load to reach PF 0.99
Present PFkVAR per kWFor 50 kW
0.601.19160 kVAR
0.651.02751 kVAR
0.700.87844 kVAR
0.750.73937 kVAR
0.780.66033 kVAR
0.800.60830 kVAR
0.850.47724 kVAR
0.900.34217 kVAR
0.950.1869 kVAR